2x 10" Min.
Figure 6-4. Condensate drained through piping loop seal.
Make sure outlet of loop seal is below bottom of HumidiPack
header.
NOTE: When installing HumidiPack for use with an electric or steam-to-steam
humidifier, minimize the length of piping run from the humidifier to Humidi-
Pack. Piping should not extend longer than 20 feet and should be a generous
size (at least 2"). Consult factory if longer piping is necessary.
Slope piping back toward humidifier or toward a drainage point. Pipe a loop
trap to an atmospheric drain at any low points in piping run. Install, at
minimum, a 10" loop seal from the HumidiPack header drain connection.
Air
Flow
Minimum
10" High
Water Seal
Figure 6-2. Drain traps discharging to floor drain.
(HumidiPackPlus shown)
Figure 6-1. Header drain trap discharging to pumped return
(HumidiPack shown)
Strainer
Drip
Leg
Header
From
Boiler
Active Tubes
F&T Trap
Inactive Tubes
6" - 12" Min.
Atmospheric
Condensate
Return
Angle Iron
Mounting Frame
Control Valve
Control Valve
From Boile
r
From Boile
r
Header
Strainer
Drip
Leg
1" Air Gap
1"/12" Slope
X
Drain
Drain
F&T Trap
Dispersion Manifold
Inactive Tubes
F&T Trap
X = 6" - 12" Min.
Control Valve
From Boile
r
Strainer
Drip Leg
Header
Angle Iron
Mounting Frame
C
1"/12" Slope
1" Air Gap
F&T Trap
Drain
Drain
F&T Trap
Active Tubes
Inactive Tubes
Elevation View
Side View
Plan View
B
(overall height)
A
Overall Width
C
F
E
D
Figure 6-3. HumidiPack CF. Drain traps discharging
to floor drain.
Figure 6-5. Dual Panel Flanged HumidiPack System.
Both "P" traps drained to atmospheric drain.